Model E Fusible Link (Short Hooks)
December 10, 2015Model Y Fusible Link (No Hooks)
December 10, 2015Model E Fusible Link (Long Hooks)
$1.66 – $5.20
Length 1.625
Width 0.875
Distance between centers – 1.00
For loads 2 to 50 pounds inclusive.
Temperatures: Listed in 165, 212, 350, and 360 degrees F.
Temperatures: Non UL Listed in 135 degrees F.
Special temperatures available.
*Links loaded linearly.With or without hooks:
Reinforced openings at both ends allow attachment
of straps, hooks and other connectors.
This thermal release fire protection device is used in the Heating, Ventilating, Air Conditioning, and Refrigeration (HVAC&R) industry, fire door applications, on overhead doors and skylights as well as other mechanical configurations for fire safety.
Elsie Manufacturing has a three week lead time for the manufacture of your products on most orders. Orders with the quantity ordered under a hundred having a temperature of 165° and 212° may be shipped sooner.
We do not accept orders under $25.00.
For orders of over 2500 pieces email info@elsiemfg.com or call Toll Free +1 800-538-4163 during business hours.
Pricing for Fusible Link Model E with Long Hooks | ||||||
---|---|---|---|---|---|---|
Temperature | ||||||
Quantity | 135°F | 165°F | 212°F | 286°F | 350°F | 360°F |
1-99 | $5.20 | $1.66 | $1.93 | $2.28 | $3.46 | $2.77 |
100-499 | $4.63 | $1.48 | $1.72 | $2.03 | $3.09 | $2.46 |
500-2499 | $4.20 | $1.32 | $1.55 | $1.83 | $2.79 | $2.23 |
2500+ | Further ranges with reduced prices, email info@elsiemfg.com or call Toll Free +1 800-538-4163 during business hours. |
Call for pricing for Model E fusible links with long hooks at 155°F, 386°F, or 536°F temperatures.
Model E Data Sheet
Operating Temperatures: 165F, 212F, 250F, 286F, 350F, 360F
Underwriters Laboratory Listed: Yes
Operating Temperature*: 135F
Underwriters Laboratory Listed: No
Loading
Minimum: 2 lbs
Maximum: 50 lbs
Size:
Length: 1.626 Inches
Width: 0.875 Inches
Distance Between Centers: 1.000 Inches
Material:
Stamping: .048 Steel
Solder: Bismuth Alloy
Unit Weight: .033 lbs
Acceptable Max. Ambient Temperatures For Specific Fusible Link Ratings. **
Fusible Link Rating: | Maximum Recommended Ambient Temperature: |
---|---|
135F (57C) | 100F (38C) |
165F (74C) | 100F (38C) |
212F (100C) | 150F (66C) |
286F (141C) | 225F (107C) |
350F (177C) | 300F (149C) |
360F (182C) | 300F (149C) |
* Many other Temperatures Available (non-UL listed)